| Standby
Power Systems |
| Environmentally
Friendly, Quiet,
Reliable, AC Power |
|
|
| Output Voltage (VAC) |
220 RMS ± 5% |
| Output Frequency |
50 Hz ± 0.05% |
| Output Waveform |
Quasi-sine wave, with
waveform stabilizer |
| Input Voltage (VDC) |
22 to 28 |
| Operating
Temperature |
-20° to 40°C
(0° to 104°F) |
| Efficiency |
Up to 93% |
|

|
 |
|
|
Other Design Features:
- Thermally-controlled cooling fan
- Enclosed AC and DC cable connections with
strain relief
- Remote ON/OFF switch hookup
- LED indications of Inverter Power, Low Input
Voltage, Overload, and High Temperature
- Battery voltage indicator with push-to-test
- LED indication of Battery Charger On, 100%
charge level, 80% charger level, & Timer Complete
|
Unit Protection:
- Automatic electronic short circuit/overload protection
- Automatic high temperature shutdown
- Output circuit breaker
Battery Protection:
- Automatic low battery shutdown at 21 volts (with in-rush delay)
|
|
| 24V Input Models |
24U15BFT |
24X24BFT |
| Documentation |
 |
| Output Power (Watts
Cont.) |
1,500 |
2,400 |
|
Output Current (Amps AC) |
Up
to 7 |
Up to
11 |
|
Peak Output (Amps AC) |
18 |
33 |
| Output
Rating (horsepower) |
¼ |
¾ |
|
Input Current (Amps DC) |
Up
to 75 |
Up to
120 |
|
Weight (lbs.) |
35 |
56 |
|
Dimensions (in.)
LxWxH |
13¼
x 11 x 6¾ |
14½ x 11½ x 7¾ |
| BATTERY
CHARGER "B" |
Totally
Correct ®, selectable between wet and sealed lead acid batteries, selectable between small and large battery banks |
| Output
Current (Amps DC) |
50 |
75 |
| Input
Current (Amps AC) |
Up
to 10 |
Up to 15 |
| TRANSFER
RELAY "T" |
|
| Current
Rating (Amps AC) |
30 |
| Transfer
Time (milliseconds) |
less
than 35 |
|
Usage: Any
220 VAC, 50 Hz, product within the inverters power
rating that does not require a pure sine waveform.
Warranty: Full year parts and factory labor |
| |
|